When testing
between a 25-gauge metal stud and a 20 or 16 gauge metal stud, tests show that there
are measurable decreases in STC values as the stud becomes heavier and as the
spacing between studs decreases. The testing results show that when comparing
similar partitions, a 25-gauge metal stud wall was usually 4-5 STC points
higher than 20- and 16-gauge stud walls. Also, by comparing similar partitions,
the results show that there is a 3-4 STC point drop between walls when studs
are installed 406 mm (16”) on center rather than 610 mm (24”) on center. There
was really no significant difference in STC value between partitions with
16-gauge studs and 20-gauge studs. Based on the test results measurements, the
walls in question in order to comply with the STC guideline for partitions
between exam rooms referenced here, a double-stud partition would be required. In other words, heavier gauge metal studs
perform no better than wood because of the loss of STC values.
Sunday, April 7, 2013
Thursday, November 15, 2012
Monday, September 17, 2012
STC Ratings Simply Put
Sound Transmission Class (STC) is an integer rating of how well a framed wall attenuates sound.
• Doubling the mass of a wall assembly does not double the STC
• An empty framed wall (steel studs and a layer of gypsum wallboard on each side) has an STC of approximately 35dB
• Adding an additional layer of gypsum wallboard (from two sheets to four sheets) increases the STC by about 5–6 points
• Adding cavity insulation increases the STC approximately 4–6 dB
• Fiberglass batts increase the STC to 39; Cellulose insulation increases the STC to 44
• Batt insulation must fit tight without gaps
• Batt thickness provides better sound control than batt density. Compressing a batt reduces STC and thermal efficiency
• Stud assembly must span from deck to ceiling
• Structurally decoupling the gypsum wallboard panels from each other, like using a staggered stud assembly
or a double stud wall) can yield an STC as high as 63 or more
•Also materials such as United Plastics Corporation's dB-3PRO along with gypsum wallboard and insullation may also improve STC ratings (Refer to manufacturer specifications)
Wednesday, September 5, 2012
How Loud is TOO LOUD
Standards set by OSHA (Occupational Safety and Health Administration) indicate that continued exposure to noise over 85 dBA will eventually harm hearing. According to OSHA, the exposure time allowed is cut in half for every 5 decibel increase. For example, if a sound is 95 dBA, then 4 hours of exposure, over time, will cause hearing loss, and exposure to sounds at 115 dBA for just 15 minutes a day, over time, will cause hearing loss. Other groups, such as NIOSH (National Institute for Occupational Safety and Health) calculate safe exposure time by decreasing time in half for every 3 decibel increase. The NHCA (National Hearing Conservation Association) is an excellent resource for more information about occupational hearing conservation programs.
Tuesday, June 19, 2012
Will this really control sound?
Resilient channel is a specially-formed, metal device that,
when used to hang drywall (instead of attaching the drywall directly to the wall
studs or ceiling joists), significantly reduces the sound transmission of the
wall or ceiling system. The channel material is secured to the studs and drywall
is secured to the channel - providing a break in sound transmission through the
wall.
Resilient channel for sound control is not effective if
attached to sheet materials, such as drywall. It is also important to use the
right length screws, so they do not penetrate into the wood framing.
Just a few screws into the wood can undermine the resilient
connection and substantially lower the STC and IIC ratings.
Monday, June 4, 2012
Did you know?
Resilient Channel was not originally designed to provide improved sound attenuation,
but rather to avoid cracks in drywall?
Tuesday, May 22, 2012
More and more States are adopting ordinances for dealing with sound
Here is an example of what one state is doing:
Table 1 - State noise guidelines.
|
State Department of Health and County Liquor
Commission Maximum Permissible Noise Limits
|
||
|
Zoning Districts:
|
Daytime
(7:00 am to 10:00 pm) |
Nighttime
(10:00 pm to 7:00 am) |
|
Residential, Conservation,
Preservation, Public/Open Space
|
55 dBA
|
45 dBA
|
|
Multi-Family Dwellings, Apartments, Business,
Commercial, Hotel, Resort
|
60 dBA
|
50 dBA
|
|
Agriculture, Country, Industrial
|
70 dBA
|
70 dBA
|
|
County Land Use
Commission Special Ordinance for Outdoor Amphitheater
|
||
|
Nearest Apartment/Hotel/Business (approximately 2000
feet away)
|
68 dBA
|
Prohibited
|
Tuesday, April 17, 2012
How does NOISE effect us in everyday life?
When unwanted sound created by human beings hits our ears and disturbs the environment, noise pollution is created. Chiefly, noise pollution comes from barking dogs, loud music, vehicles, aircraft and rail transport, air-conditioners, factories, amplified music and construction work.
Sources of noise: All transportation systems create noise pollution. With residences created adjacent to factories, they experience noise pollution and its adverse effects. Besides transportation noise, noise can come from factory appliances, power tools and audio entertainment systems.
Measures of noise: Noise pollution is measured in decibels. When noise is at 45 decibels, no human being can sleep, and at 120 decibels the ear is in pain and hearing begins to be damaged at 85 decibels.
Effects of noise pollution
Human health: Noise pollution disturbs our health and behavior in a number of ways including deafness causing lack of sleep, irritability, indigestion, heartburn, high blood pressure, ulcers, and heart disease. Just one noise explosion from a passing truck drastically alters our endocrinal, neurological, and cardiovascular functions in many individuals. If this is prolonged or frequent, the physiological disturbances become chronic and contribute to mental illness.
Annoyance: Sometimes, even low levels of noise are irritating and can be frustrating, and high volumes can be annoying. Natural sounds are less irritating than those we find uncontrollable but intermittent sounds such as a tap dripping water can be more irritating than the sound of falling rain.
Sources of noise: All transportation systems create noise pollution. With residences created adjacent to factories, they experience noise pollution and its adverse effects. Besides transportation noise, noise can come from factory appliances, power tools and audio entertainment systems.
Measures of noise: Noise pollution is measured in decibels. When noise is at 45 decibels, no human being can sleep, and at 120 decibels the ear is in pain and hearing begins to be damaged at 85 decibels.
Effects of noise pollution
Human health: Noise pollution disturbs our health and behavior in a number of ways including deafness causing lack of sleep, irritability, indigestion, heartburn, high blood pressure, ulcers, and heart disease. Just one noise explosion from a passing truck drastically alters our endocrinal, neurological, and cardiovascular functions in many individuals. If this is prolonged or frequent, the physiological disturbances become chronic and contribute to mental illness.
Annoyance: Sometimes, even low levels of noise are irritating and can be frustrating, and high volumes can be annoying. Natural sounds are less irritating than those we find uncontrollable but intermittent sounds such as a tap dripping water can be more irritating than the sound of falling rain.
Friday, April 13, 2012
Here Are A Few Examples Of Sounds Effects on Education and Healthcare
Noise Levels In Education
Cognitive development is impaired when homes or schools are near sources of noise such as highways and airports.
Noise affects learning, reading, problem solving, motivation, school performance, and social and emotional development.
Children who live in noisy environments have been shown to have elevated blood pressures and elevated levels of stress-induced hormones.
American National Standards Institute calls for a maximum ambient noise level of 35 dB.
Many classrooms currently do not meet the recommendations of this standard, but at least one state, Connecticut, has already adopted the use of ANSI S12.60 for its schools.
Noise Levels In Healthcare
Excessive noise, and its effect on rest, are high on the list of complaints made by patients on post-discharge patient satisfaction surveys.
Excessive noise in health care settings can induce headaches, cause irritability, prolong wound healing and increase sensitivity to pain.
Noise levels in hospitals are twice what they were a few decades ago. They're approaching the level of harm, and they're definitely at the level of stress.
Health care is noisier than ever. Worldwide, the sound levels inside hospitals average 72 decibels during the day and 60 decibels at night — far exceeding the standard of 40 decibels or less, set by the World Health Organization.
Did you know ... ? Tapping on the top of an incubator is equivalent to the sounds of heavy traffic during rush hour!
In her 1859 book "Notes on Nursing," Florence Nightingale railed against unnecessary noise, calling it "the most cruel absence of care."
Tuesday, March 6, 2012
Noise Mitigation or Abatement It's a Constant Concern
Architectural solutions
Regarding sound generated inside the building, there are two principal types of transmission. Firstly, airborne sound travels through walls or floor and ceiling assemblies and can emanate from either human activities in adjacent living spaces or from mechanical noise within the building systems. Human activities might include voice, amplified sound systems or animal noise. Mechanical systems are elevator systems, boilers, refrigeration or air conditioning systems, generators and trash compactors. Since many of these sounds are inherently loud, the principal design element is to require the wall or ceiling assembly to meet certain performance standards[7] (typically Sound transmission class of 50), which allows considerable attenuation of the sound level reaching occupants.
The second type of interior sound is called Impact Insulation Class (IIC) transmission. This effect arises not from airborne transmission, but rather from transmission of sound through the building itself. The most common perception of IIC noise is from footfall of occupants in living spaces above. This type of noise is more difficult to abate, but consideration must be given to isolating the floor assembly above or hanging the lower ceiling on resilient channel.
Both of the above transmission effects may emanate either from building occupants or from building mechanical systems such as elevators, plumbing systems or heating, ventilating and air conditioning units. In some cases it is merely necessary to specify the best available quieting technology in selecting such building hardware. In other cases shock mounting of systems to control vibration may be in order. In the case of plumbing systems there are specific protocols developed, especially for water supply lines, to create isolation clamping of pipes within building walls. In the case of central air systems, it is important to baffle any ducts that could transmit sound between different building areas.
Designing special purpose rooms has more exotic challenges, since these rooms may have requirements for unusual features such as concert performance, sound studio recording, lecture halls. In these cases reverberation and reflection must be analyzed in order to not only quiet the rooms but prevent echo effects from occurring. In these situations special sound baffles and sound absorptive lining materials may be specified to dampen unwanted effects.
Main article: Architectural acoustics
Beyond the interior acoustics cited above under aircraft noise, there has been a steady trend to design quieter buildings with regard to sources within and without the structure itself.[citation needed] In the case of construction of new (or remodeled) apartments, condominiums, hospitals and hotels, many states and cities have stringent building codes with requirements of acoustical analysis, in order to protect building occupants. With regard to exterior noise, the codes usually require measurement of the exterior acoustic environment in order to determine the performance standard required for exterior building skin design. The architect can work with the acoustical scientist to arrive at the best cost-effective means of creating a quiet interior (normally 45 dBA). The most important elements of design of the building skin are usually: glazing (glass thickness, double pane design etc.), roof material, caulking standards, chimney baffles, exterior door design, mail slots, attic ventilation ports and mounting of through the wall air conditioners.Regarding sound generated inside the building, there are two principal types of transmission. Firstly, airborne sound travels through walls or floor and ceiling assemblies and can emanate from either human activities in adjacent living spaces or from mechanical noise within the building systems. Human activities might include voice, amplified sound systems or animal noise. Mechanical systems are elevator systems, boilers, refrigeration or air conditioning systems, generators and trash compactors. Since many of these sounds are inherently loud, the principal design element is to require the wall or ceiling assembly to meet certain performance standards[7] (typically Sound transmission class of 50), which allows considerable attenuation of the sound level reaching occupants.
The second type of interior sound is called Impact Insulation Class (IIC) transmission. This effect arises not from airborne transmission, but rather from transmission of sound through the building itself. The most common perception of IIC noise is from footfall of occupants in living spaces above. This type of noise is more difficult to abate, but consideration must be given to isolating the floor assembly above or hanging the lower ceiling on resilient channel.
Both of the above transmission effects may emanate either from building occupants or from building mechanical systems such as elevators, plumbing systems or heating, ventilating and air conditioning units. In some cases it is merely necessary to specify the best available quieting technology in selecting such building hardware. In other cases shock mounting of systems to control vibration may be in order. In the case of plumbing systems there are specific protocols developed, especially for water supply lines, to create isolation clamping of pipes within building walls. In the case of central air systems, it is important to baffle any ducts that could transmit sound between different building areas.
Designing special purpose rooms has more exotic challenges, since these rooms may have requirements for unusual features such as concert performance, sound studio recording, lecture halls. In these cases reverberation and reflection must be analyzed in order to not only quiet the rooms but prevent echo effects from occurring. In these situations special sound baffles and sound absorptive lining materials may be specified to dampen unwanted effects.
Noise Polllution Another Man-made Problem and Only Getting Worse
noise pollution
noise pollution, human-created noise harmful to health or welfare. Transportation vehicles are the worst offenders, with aircraft, railroad stock, trucks, buses, automobiles, and motorcycles all producing excessive noise. Construction equipment, e.g., jackhammers and bulldozers, also produce substantial noise pollution.
Noise intensity is measured in decibel units. The decibel scale is logarithmic; each 10-decibel increase represents a tenfold increase in noise intensity. Human perception of loudness also conforms to a logarithmic scale; a 10-decibel increase is perceived as roughly a doubling of loudness. Thus, 30 decibels is 10 times more intense than 20 decibels and sounds twice as loud; 40 decibels is 100 times more intense than 20 and sounds 4 times as loud; 80 decibels is 1 million times more intense than 20 and sounds 64 times as loud. Distance diminishes the effective decibel level reaching the ear. Thus, moderate auto traffic at a distance of 100 ft (30 m) rates about 50 decibels. To a driver with a car window open or a pedestrian on the sidewalk, the same traffic rates about 70 decibels; that is, it sounds 4 times louder. At a distance of 2,000 ft (600 m), the noise of a jet takeoff reaches about 110 decibels—approximately the same as an automobile horn only 3 ft (1 m) away.
Subjected to 45 decibels of noise, the average person cannot sleep. At 120 decibels the ear registers pain, but hearing damage begins at a much lower level, about 85 decibels. The duration of the exposure is also important. There is evidence that among young Americans hearing sensitivity is decreasing year by year because of exposure to noise, including excessively amplified music. Apart from hearing loss, such noise can cause lack of sleep, irritability, heartburn, indigestion, ulcers, high blood pressure, and possibly heart disease. One burst of noise, as from a passing truck, is known to alter endocrine, neurological, and cardiovascular functions in many individuals; prolonged or frequent exposure to such noise tends to make the physiological disturbances chronic. In addition, noise-induced stress creates severe tension in daily living and contributes to mental illness.
Noise is recognized as a controllable pollutant that can yield to abatement technology. In the United States the Noise Control Act of 1972 empowered the Environmental Protection Agency to determine the limits of noise required to protect public health and welfare; to set noise emission standards for major sources of noise in the environment, including transportation equipment and facilities, construction equipment, and electrical machinery; and to recommend regulations for controlling aircraft noise and sonic booms. Also in the 1970s, the Occupational Safety and Health Administration began to try to reduce workplace noise. Funding for these efforts and similar local efforts was severely cut in the early 1980s, and enforcement became negligible.
The Columbia Electronic Encyclopedia, 6th ed. Copyright © 2007, Columbia University Press. All rights reserved.
Read more: noise pollution — Infoplease.com http://www.infoplease.com/ce6/sci/A0835810.html#ixzz1oMyBMgZu
Monday, January 30, 2012
A Brief Histroy of Resilient Channel
History of Resilient Channel:
Resilient Channel was originally brought to the mass market decades ago by USG (United States Gypsum). The product was trademarked as RC-1, and tested extensively at Riverbank Acoustic Laboratories. Today many installers, architects and material retailers refer to any channel with one “leg” as RC-1. It’s important to note that USG hasn’t dealt with the original resilient channel design for years and years. Since then, many manufacturers have made a “resilient channel” and informally referred to previous USG test data for acoustic performance. This is entirely misleading and quite unfortunate. Resilient channel available today has many profiles, mil thicknesses and performance characteristics, so it really not possible to simply predict how any given piece of “resilient channel” will perform. Additionally any 1 or 2 legged resilient channel is not specified by the Steel Stud Manufacturers Association (SSMA). So there are no standards for its construction or use.Saturday, January 7, 2012
How Acoustic Barriers Reduce Sound
Anyone who's ever shared a wall with someone else has probably wondered if the walls were intentionally thin, or the neighbors intentionally loud. Often the assumption is that the walls between dwellings simply need to be thicker to muffle sound. The fact is that the design of the wall, not the size, can be a contributing factor in transmitting sound from one side to the other.
Consider how walls are constructed in most multi-family housing units. Basically, they are made of gypsum board firmly attached to both sides of a wood frame. When sound waves hit one side of the wall it causes the gypsum board on that side to vibrate. Since the gypsum board is rigidly connected to the frame, the vibration is transmitted right through the framing to the gypsum board on the other side. Those same vibrations travelling through the wall frame can also send sound throughout adjacent floors and ceilings. Noises will radiate through the structure because there's almost nothing there to cushion or absorb the sound waves.
In order to significantly dampen those approaching sound waves, United Plastics Corporation’s dB-3 Pro can be installed between one of the gypsum walls and the frame. The United Plastics Corporation dB-3 Pro, which is made of 100% post-industrial materials acts as a shock absorber in this system, muffling vibrations coming from either side of the wall. United Plastics Corporation’s dB-3 Pro is an improvement over the resilient channel system’s that are routinely used to improve the sound ratings for walls and are especially effective in floor/ceiling constructions.
Resilient channels typically add 3 to 5 Sound Transmission Class (STC) points to an otherwise identical wall or ceiling, whereas United Plastics Corporation’s dB-3 Pro up’s the ante by adding between 3-5 Sound Transmissions Class (STC) points per layer. This can most often is more than enough to meet the STC and Impact Insulation Class (IIC) ratings required by the project design goals or local codes. In California, the building code specifies minimum lab tested ratings of STC 50 and IIC 50 for partitions in multi-family dwellings.
In fact, the IIC 50 rating required by the building code is easily achieve using the dB-3 Pro wall material when hung in the ceiling in a multi-family project. Unless the floors are completely carpeted (which is rare for kitchens and bathrooms), it is very difficult to achieve IIC 50 ratings without using resilient channels and batt insulation in the floor-ceiling constructionJust what is the difference between Structure-borne and Air-borne noise?
| The noise given off by a particular source can usually be categorised into one of the following forms: Structure-borne noiseThis is the sound generated from a vibrating source or impact event. The acoustic energy created by these vibrations is transmitted into the structure of a building (e.g. floors, walls, pipe-work etc,) or into mechanical elements (e.g. metal frames, panel work, supports etc.) This energy travels through solid structures and is released as air-borne noise at different locations within the building or mechanical system. Air-borne noise This is the sound that travels through the air and into the surrounding environment. In closed environments such as rooms and enclosures, air-borne sound may reverberate and increase the levels of noise both in and outside the contained space. Most forms of noise will contain contributions from both air-borne and structure-borne sound. Although measures can be taken to limit structure-borne components, such as by isolation and damping, air-borne sound can be treated with the use of absorbing materials. ArmaSound RD has an extremely high absorption performance per unit thickness, offering a solution for the most demanding applications. | |
By way of example, someone who is hammering a nail into a wall (See diagram) will create structural noise, causing vibration of the surrounding structure. However, they will create a significant amount of air-borne noise, which will be clearly heard in the room where the action is taking place. As the noise travels, it may also change forms. I.e. Structure-borne noise may eventually cause sympathetic vibrations in other structures and release airborne sound. In this example, the structure borne components of the noise may travel towards the light fitting that’s in the same room causing it to shake and release audible clatter. Airborne noise may also change into structure-borne and back to air-borne. This process is often called ‘transmission’ of sound energy. Once again, in the example above, the air-borne components of the noise may travel into the far wall, and then out through the other side and into an adjoining room. |
Wednesday, December 28, 2011
Noise - A Universal Complaint
Noise - A Universal Complaint
According to a recent Daily News poll, most New Yorkers cite NOISE as the most annoying feature of urban life(1). Furthermore, when the NYC Police Department instituted its quality of life telephone hotline in August, 1996, 43% of complaints received related to noise(2).
The noise that annoys New Yorkers comes in many forms from many places. Shrieking subways(3), thudding pile drivers(4), roaring boilers(5), noisy neighbors(6), raucous restaurants(7). Community meetings throughout the City regularly address the failure or refusal of City agencies to effectively respond to noise complaints.
Excessive Noise is Unhealthy
Excessive noise is hazardous to our physical and mental health(8). The body reacts to unwelcome noise of any intensity indirectly as it does to other intrusive stressful stimuli: elevated blood pressure, excessive secretion of hormones, changes in the rhythm of the heart. There is a growing body of literature that suggests that these physiological responses may lead to actual bodily damage in adults and in children(9). In addition, the frustration of not being able to limit distracting noise compounds the body's physiological responses. In some cases, noise drives people to commit homicide or suicide
Wednesday, December 21, 2011
If this is a sign of the times then Sound Control best be on everyone's mind
Reprinted from Associated Press Tuesday, December 20, 2011
Rise in home building suggests industry turnaround
Dec. 20, 2011, 1:46 p.m. EST
AP
WASHINGTON (AP) — A surge in apartment construction gave home builders more work in November. And permits, a gauge of future construction, rose largely because of a jump in apartment permits.
Some analysts say the gains, though coming off extremely low levels, suggest the depressed housing industry may have reached a turning point.
Economists now say 2011 will be the first year since the Great Recession began in 2007 that home construction will have helped the economy grow. Before this year, the industry endured two of the worst years ever.
"Homebuilding is through the worst and is now steadily improving," said Paul Diggle, a property economist at Capital Economics.
Builders broke ground on a seasonally adjusted annual rate of 685,000 homes in November, a 9.3 percent jump from October, the government said Tuesday. It's the highest level since April 2010.
Still, the rate is far below the 1.2 million homes that economists say would be built each year in a healthy housing market.
Construction of single-family homes rose 2.3 percent in November to a seasonally adjusted annual rate of 447,000. Apartment construction jumped 32 percent to a rate of 238,000 units. Single-family homes account for about 70 percent of homebuilding.
For the year, work is expected to have begun on 430,000 single-family homes and 185,000 apartments. Those figures remain far below the roughly 840,000 single-family homes and 360,000 apartments that would be started in a healthy economy.
Tuesday's home construction data, along with encouraging economic news out of Germany and Spain, helped fuel a huge rally on Wall Street. The Dow Jones industrial average jumped more than 300 points, or 2.7 percent, by mid-afternoon.
Patrick Newport and Michelle Valverde, U.S. economists at IHS Global Insight, said the better-than-expected figures show that the housing industry is "finally getting off the mat."
"It'll keep getting better through next year," said Jared Franz, an associate economist at T. Rowe Price.
Last year, builders began work on roughly 587,000 homes. That barely surpassed the 554,000 homes started in 2009, the worst year ever.
Though new homes represent just 20 percent of the overall home market, they have an outsize impact on the economy. Each home built creates an average of three jobs for a year and generates about $90,000 in taxes, according to the National Association of Home Builders.
Renting has become a preferred option for many Americans who lost their jobs during the recession and were forced to leave their houses. The surge in apartments has provided a lift to the beleaguered housing market but has not been enough to completely offset the loss of single-family homes.
Permits rose 5.7 percent last month to a seasonally adjusted annual rate of 681,000, boosted by a 16 percent jump in permits for apartment buildings, to 246,000.
Builders typically begin construction on single-family homes six months after getting a permit. With apartment projects, the lag time can be up to a year.
Over the past year, permits for apartment buildings with five or more units have surged more than 80 percent. Permits for single-family homes have risen much less: just 3.6 percent.
Demand for new homes is weak. Record-low mortgage rates and plunging home prices have done little to help.
The chief problem: Builders are struggling to compete with deeply discounted foreclosures and short sales. Short sales occur when lenders allow homes to be sold for less than what's owed on the mortgage. Few homes are selling.
After previous recessions, housing accounted for at least 15 percent of U.S. economic growth. Since the recession officially ended in June 2009, it has contributed just 4 percent.
In October, sales of new homes rose slightly, largely because builders cut their prices in the face of weak demand. Sales hit a six-month low in August. And this year is shaping up to be the worst since the government began keeping records a half-century ago.
Another reason sales have fallen is that previously occupied homes have become a better deal than new homes. The median price of a new home is about 30 percent higher than the median price for a re-sale. That's nearly twice the markup typical in a healthy housing market.
The homebuilders' trade group said this week that its survey of industry sentiment rose in December to 21, the highest level since May 2010. Still, any reading below 50 indicates negative sentiment about the housing market. The index hasn't reached 50 since April 2006, the peak of the housing boom.
Some analysts say the gains, though coming off extremely low levels, suggest the depressed housing industry may have reached a turning point.
Economists now say 2011 will be the first year since the Great Recession began in 2007 that home construction will have helped the economy grow. Before this year, the industry endured two of the worst years ever.
"Homebuilding is through the worst and is now steadily improving," said Paul Diggle, a property economist at Capital Economics.
Builders broke ground on a seasonally adjusted annual rate of 685,000 homes in November, a 9.3 percent jump from October, the government said Tuesday. It's the highest level since April 2010.
Still, the rate is far below the 1.2 million homes that economists say would be built each year in a healthy housing market.
Construction of single-family homes rose 2.3 percent in November to a seasonally adjusted annual rate of 447,000. Apartment construction jumped 32 percent to a rate of 238,000 units. Single-family homes account for about 70 percent of homebuilding.
For the year, work is expected to have begun on 430,000 single-family homes and 185,000 apartments. Those figures remain far below the roughly 840,000 single-family homes and 360,000 apartments that would be started in a healthy economy.
Tuesday's home construction data, along with encouraging economic news out of Germany and Spain, helped fuel a huge rally on Wall Street. The Dow Jones industrial average jumped more than 300 points, or 2.7 percent, by mid-afternoon.
Patrick Newport and Michelle Valverde, U.S. economists at IHS Global Insight, said the better-than-expected figures show that the housing industry is "finally getting off the mat."
"It'll keep getting better through next year," said Jared Franz, an associate economist at T. Rowe Price.
Last year, builders began work on roughly 587,000 homes. That barely surpassed the 554,000 homes started in 2009, the worst year ever.
Though new homes represent just 20 percent of the overall home market, they have an outsize impact on the economy. Each home built creates an average of three jobs for a year and generates about $90,000 in taxes, according to the National Association of Home Builders.
Renting has become a preferred option for many Americans who lost their jobs during the recession and were forced to leave their houses. The surge in apartments has provided a lift to the beleaguered housing market but has not been enough to completely offset the loss of single-family homes.
Permits rose 5.7 percent last month to a seasonally adjusted annual rate of 681,000, boosted by a 16 percent jump in permits for apartment buildings, to 246,000.
Builders typically begin construction on single-family homes six months after getting a permit. With apartment projects, the lag time can be up to a year.
Over the past year, permits for apartment buildings with five or more units have surged more than 80 percent. Permits for single-family homes have risen much less: just 3.6 percent.
Demand for new homes is weak. Record-low mortgage rates and plunging home prices have done little to help.
The chief problem: Builders are struggling to compete with deeply discounted foreclosures and short sales. Short sales occur when lenders allow homes to be sold for less than what's owed on the mortgage. Few homes are selling.
After previous recessions, housing accounted for at least 15 percent of U.S. economic growth. Since the recession officially ended in June 2009, it has contributed just 4 percent.
In October, sales of new homes rose slightly, largely because builders cut their prices in the face of weak demand. Sales hit a six-month low in August. And this year is shaping up to be the worst since the government began keeping records a half-century ago.
Another reason sales have fallen is that previously occupied homes have become a better deal than new homes. The median price of a new home is about 30 percent higher than the median price for a re-sale. That's nearly twice the markup typical in a healthy housing market.
The homebuilders' trade group said this week that its survey of industry sentiment rose in December to 21, the highest level since May 2010. Still, any reading below 50 indicates negative sentiment about the housing market. The index hasn't reached 50 since April 2006, the peak of the housing boom.
Tuesday, December 20, 2011
Just how do you calculate STC ratings?
For those of you that want to know how to calculate STC, here it is:
Measure the transmission loss (TL) for the wall system from 125 Hz to 4 kHz and plot on a chart. The STC for the wall is determined by superimposing a contour chart (not shown here) upon the TL curve such that (1) there is no more than a 8-dB deficiency between the TL and the STC contour at any 1/3-octave frequency (i.e., no test point may be more than 8 dB below the STC contour), and (2) the total deficiency between the STC contour and the TL curve (i.e., the value of the STC contour minus the value of the TL curve summed at all 1/3-octave frequencies from 125Hz to 4 kHz) must be less than or equal to 32 dB. Once the curve has been adjusted to met these two criteria, then the STC value of the wall is equal to the TL value of the contour at 500 Hz.
Makes sense? Not really!
Best way to say it is: The more noise the wall system reduces – the higher the STC number.
Monday, December 5, 2011
Building Codes
In the case of construction of new (or remodeled) apartments, condominiums, hospitals and hotels, many U.S. states and cities have stringent building codes with requirements of acoustical analysis, in order to protect building occupants from exterior noise sources and sound generated within the building itself.[8]. With regard to exterior noise, the codes usually require measurement of the exterior acoustic environment in order to determine the performance standard required for exterior building skin design. The architect can work with the acoustical scientist to arrive at the best cost-effective means of creating a quiet interior (normally 45 dBA). The most important elements of design of the building skin are usually: glazing (glass thickness, double pane design, etc.), roof material, caulking standards, chimney baffles, exterior door design, mail slots, attic ventilation ports and mounting of through the wall air conditioners. A special case of building skin design arises in the case of aircraft noise, where the FAA has funded extensive work in residential retrofit.
Regarding sound generated inside the building, there are two principal types of transmission. First, airborne sound travels through walls or floor/ceiling assemblies and can emanate from either human activities in adjacent living spaces or from mechanical noise within the building systems. Human activities might include voice, amplified sound systems or animal noise. Mechanical systems are elevator systems, boilers, refrigeration or air conditioning systems, generators and trash compactors. Since many of these sounds are inherently loud, the principle of regulation is to require the wall or ceiling assembly to meet certain performance standards (typically Sound Transmission Class of 50), which allows considerable attenuation of the sound level reaching occupants.
The second type of interior sound is called Impact Insulation Class (IIC) transmission. This effect arises not from airborne transmission, but rather from transmission of sound through the building itself. The most common perception of IIC noise is from footfall of occupants in living spaces above. This type of noise is somewhat more difficult to abate, but consideration must be given to isolating the floor assembly above or hanging the lower ceiling on resilient channel. Commonly a performance standard of IIC equal to 50 is specified in building codes. California has generally led the U.S. in widespread application of building code requirements for sound transmission; accordingly, the level of protection for building occupants has increased markedly in the last several decad
Regarding sound generated inside the building, there are two principal types of transmission. First, airborne sound travels through walls or floor/ceiling assemblies and can emanate from either human activities in adjacent living spaces or from mechanical noise within the building systems. Human activities might include voice, amplified sound systems or animal noise. Mechanical systems are elevator systems, boilers, refrigeration or air conditioning systems, generators and trash compactors. Since many of these sounds are inherently loud, the principle of regulation is to require the wall or ceiling assembly to meet certain performance standards (typically Sound Transmission Class of 50), which allows considerable attenuation of the sound level reaching occupants.
The second type of interior sound is called Impact Insulation Class (IIC) transmission. This effect arises not from airborne transmission, but rather from transmission of sound through the building itself. The most common perception of IIC noise is from footfall of occupants in living spaces above. This type of noise is somewhat more difficult to abate, but consideration must be given to isolating the floor assembly above or hanging the lower ceiling on resilient channel. Commonly a performance standard of IIC equal to 50 is specified in building codes. California has generally led the U.S. in widespread application of building code requirements for sound transmission; accordingly, the level of protection for building occupants has increased markedly in the last several decad
Saturday, November 26, 2011
C. F. Evans Construction Endorses dB-3Pro Sound Control
Building Pride
CONSTRUCTION
“We build it like it’s ours.”
The products from United Plastic Corporation are lightweight, environmentally responsible
and easy to install.
Winter 2012
Using Recycled Materials To Mitigate Sound
Living in a high-density apartment community offers many benefits and
conveniences. For those with a busy lifestyle, among the greatest conveniences
are the lack of yard work and a maintenance staff that repairs appliances and
fixes other problems free of charge that homeowners would otherwise have to pay for. In
addition, apartment dwellers enjoy the year-round use of luxurious community amenities
such as swimming pools, outdoor fire pits, dog parks and movie theaters, and most
communities these days are in excellent urban locations, within walking distance of parks,
stores and your neighbors.
Those who rent are also free to move whenever the lease ends, without worrying about
selling a home. However, one of the challenges of apartment living is dealing with the
sounds from outside one’s apartment that can travel into the living space. For developers,
sound attenuation is an extremely important aspect that must be properly addressed when
building a multi-unit building.
Sound attenuation is the combined effect of the scattering (or reflection) of sound and
the absorption of sound energy. Attenuation results in a weakening of the sound, such
as what occurs when sound travels through a medium like a wall or floor in a building.
“Human sound,” such as TV noises, talking and basic appliances, is filtered out when the
Sound Transmission Class, or STC, of a wall or floor is around 50. STC is the rating that a
wall or floor receives based on how well it filters out sound; the higher the STC, the more
effective that wall or floor is at reducing noise. Typically, builders install insulation in a wall
that filters out higher frequency noises, and often a type of blocker material is used that
can increase the STC of that wall.
C.F. Evans Named Best Places To Work Finalist
For the third year in a row, C.F. Evans Construction was named
a finalist in the Best Places to Work
in South Carolina Small to Medium
Business Category. This year, we
are extremely grateful to be named
in the Top 10. We would like to
take this opportunity to thank
our employees, clients, partners,
subcontractors and suppliers.
Without you we would not be here.
We wish you and yours a happy and
healthy New Year.
continued on page 4
CONSTRUCTION
Building Pride through
teamwork and innovation
“We build it like it’s ours.”
We’re doing our part.
This newsletter is printed on environmentally-friendly paper—50% recycled, using 25% post-consumer waste,
and is composed of a mixture of fibers from certified forests, post-consumer recycling processes and fibers from other controlled sources.
United Plastics Corporation was
founded in 1946 as Carolina Plastics
Co. and manufactured products for the
automotive industry. Located in Mount
Airy, N.C., United Plastics produces
flexible, rigid and dual durometer profiles,
PVC cellular foam profiles, flexible sheet
and roll goods for the construction,
automotive, furniture and many other
industries.
United Plastics Corporation is dedicated
to producing environmentally-friendly
products. They utilize more than 80,000
lbs. of post-industrial scrap each day
that would otherwise end up in landfills.
Products contain recycled materials and
many of their consumer and commercial
products qualify for LEED points.
There are many products that can help increase STC ratings. Recently, we learned
about several innovative products developed by United Plastics Corporation that can
assist in this effort and are environmentally responsible. dB-4looring, dB-3 for walls
and dB-2 for retrofitting are just a few solutions United Plastics has developed to assist
builders with sound control strategy. Builders can increase the STC of walls and floors
by approximately five levels per layer of sound material used. If the product is used on
both sides of a wall or floor, the STC rating can increase by 10!
Most of the sound that disturbs people is generally in the spectrum 4,000 to 5,000
Hz (hertz). “Our product performs exceptionally well within those ranges and in the
lower ranges of hertz from about 150-400, which are the bass sounds, the vibration
sounds from objects such as a subwoofer, TV or stereo,” explains John Bishop of
United Plastics.
What appeals to us most are the environmental qualities of United Plastics’
products. Most blocking materials are virgin products made from petroleum-based
materials, which means they are affected by the changes in oil prices and comprised
of a minimum of recycled materials. On the other hand, dB-3, dB-2 and dB-4looring
products are made of 100% recycled materials, and because of the amount of polyester
materials included, they are incredibly flexible. This flexibility allows the products to
scatter low frequency sounds, rather than transferring the sound through.
Another benefit of United Plastics’ products is that they are only one-eighthinch
thick. When using them, builders can use standard width jams and avoid
special allowances or floor plan changes to account for increases in thickness of the
wall as may be required with double layer drywall. Installation is as easy as drywall:
the material is very lightweight, so drywall installers can perform the work and
builders can avoid additional hiring. And if that isn’t enough, the product acts as an
impermeable vapor barrier so water/moisture will not pass through.
As construction managers, we constantly seek materials to help our clients achieve
their construction, environmental and budgetary goals. United Plastics Corporation
has developed products that offer great promise in each of these areas. For more
about the company responsible for these high-performing products, please see the
accompanying sidebar.
Recycled Materials…
continued from page 1
United Plastics has developed products for
walls, floors and retrofits. Shown here is the
dB-4looring with a tile floor
Tuesday, November 15, 2011
Just how much would a damped wall system cost for a 10K s/f project
This was taken from a Construction Blog dated June 22, 2007. I doubt if anything has changed in 4 years, it more than likely costs more to do than what was originally published.
Compare that with the price of two sheets of 4x8 5/8" drywall, along with $1/sq ft for GG. Add in the additional labor to do the 2nd sheet and you can see where the cost of the double drywall with GG is substantially cheaper than QR-II at $180/sheet. Now, if you were just doing a smaller job and didn't want to mess with the GG etc, then it can certainly be argued that QR might be easier/better to work with. But certainly not when you are doing a very large project.
ballpark estimates on a 10k Sq ft job.
QR -II - 1125 sheets = ~$202,500
No additional Labor
2250 sheets of drywall - ~$35,000
GG (120 buckets) - $25,000
Additional labor - $20,000
So, we're talking more than double for using QR vs having the crew do the same work twice. . . Not a pretty site on a large project.
So, you have to ask, is it worth the money and are you saving money? Are You?
To elaborate a bit further on QR (which btw, I think is a great product, just costly). The QR which is 5/8" thick is about $140/sheet. The QR-IIwhich is 1 3/8" thick is about $180/sheet.
Compare that with the price of two sheets of 4x8 5/8" drywall, along with $1/sq ft for GG. Add in the additional labor to do the 2nd sheet and you can see where the cost of the double drywall with GG is substantially cheaper than QR-II at $180/sheet. Now, if you were just doing a smaller job and didn't want to mess with the GG etc, then it can certainly be argued that QR might be easier/better to work with. But certainly not when you are doing a very large project.
ballpark estimates on a 10k Sq ft job.
QR -II - 1125 sheets = ~$202,500
No additional Labor
2250 sheets of drywall - ~$35,000
GG (120 buckets) - $25,000
Additional labor - $20,000
So, we're talking more than double for using QR vs having the crew do the same work twice. . . Not a pretty site on a large project.
So, you have to ask, is it worth the money and are you saving money? Are You?